What Do You Need for WELL A08 Air Quality Monitoring?

What Do You Need for WELL A08 Air Quality Monitoring?

A08 Air Quality Monitoring and Awareness is the WELL v2 feature that rewards continuous air quality monitoring. It is worth up to 2 points:

  • 1 point for installing air quality monitors that measure all the time.
  • 1 point for showing that data to the people in the building.

A08 is optional. In WELL terms it is an Optimization, not a Precondition, so a project can certify without it. But it is one of the most practical points in the Air concept, and the monitors keep telling you how the building performs long after certification.

This article covers WELL v2 and the current Performance Verification Guidebook.

Part 1: What monitors do you need?

What they must measure

At least three of these:

  • PM2.5 or PM10 (fine dust)
  • CO₂ (a sign of ventilation)
  • carbon monoxide
  • ozone
  • nitrogen dioxide
  • TVOC (chemical vapours)
  • formaldehyde

Temperature and humidity are useful, but they do not count towards the three.

In practice, MoveAir would usually choose PM2.5, CO₂ and TVOC. Together they cover particles, ventilation and chemicals. If PM2.5 is new to you, start with What Is PM2.5 and Why Should Buildings Measure It?

How many monitors

It depends on the occupiable area of the whole project:

  • under 3,250 m²: one per 325 m², minimum two
  • 3,250 to 25,000 m²: one per 500 m², minimum 10
  • over 25,000 m²: one per 1,000 m², minimum 50

Always round up. A 1,200 m² office needs 1,200 ÷ 325 = 3.7, so four monitors.

Where they go

  • 1.1 to 1.7 m above the floor, where people sit or stand
  • at least 1 m from doors, opening windows and air supply or exhaust vents
  • spread across floors, HVAC zones and the spaces people actually use

We go through placement in detail in How Many IAQ Monitors Does a WELL Project Need?

How they must work

  • measure continuously during occupied hours, at least every 15 minutes
  • meet WELL’s accuracy requirements, or be RESET Grade B or better
  • be recalibrated or replaced every three years
  • send their data to IWBI once a year through the WELL digital platform

Part 2: How do you show the data to occupants?

The second point is about awareness. People in the building should be able to see the air quality data from Part 1.

You can do that with:

  • screens in the building, or
  • a website or app, with signs telling people where to find it.

The data can show the actual numbers or a simple rating, such as good or poor. It must update at least every 15 minutes.

Part 2 only counts if Part 1 is in place.

What A08 does not do

A08 does not replace the on-site air test. Every WELL project still has to meet the A01 Air Quality precondition, which a Performance Testing Agent checks before certification.

The same monitors can still do more work. For some other air features, WELL accepts sensor data as a way to show thresholds are met. Your WELL AP can confirm which ones apply to your project.

Common mistakes

  • counting temperature and humidity as two of the three parameters
  • buying monitors before checking the accuracy and 15-minute data requirements
  • mounting monitors where installation is easy, not where people work
  • forgetting the three-year recalibration
  • putting the display where nobody looks, like a corridor people rarely use

The short version

  1. A08 is optional and worth up to 2 points.
  2. Part 1: monitors measuring at least three pollutants, every 15 minutes, in the right number and places.
  3. Part 2: show the data to occupants on screens or a website or app.
  4. Recalibrate every three years and report the data every year.

FAQ

Is A08 mandatory for WELL certification?
No. It is an Optimization. A project can certify without it.

How many points is A08 worth?
Up to 2: one for the monitors, one for showing the data to occupants.

Do temperature and humidity count?
No. You need at least three of the listed pollutants, such as PM2.5, CO₂ and TVOC.

Can I use RESET accredited monitors?
Yes. WELL accepts monitors rated RESET Grade B or better, as long as they also meet the interval, calibration and reporting rules. More on RESET in What Does RESET Air Certification Actually Require?

Does every room need a monitor?
No. The number is based on the total occupiable area, and the monitors are spread to represent the building.

Does A08 replace on-site performance testing?
No. The A01 on-site air test is still required for certification.

Planning A08 for a WELL project?

MoveAir can calculate how many monitors you need, mark up where they should go on your floor plans, and set up a dashboard that shows live data to occupants. Talk to us.

Healthy Buildings. Made Measurable.

Keep reading

Can Cleaner Classroom Air Improve Test Scores?

Can Cleaner Classroom Air Improve Test Scores?

In 2015, a huge gas leak near Los Angeles led to air filters being installed in every nearby school. Nobody planned it as an experiment, but it became one of the clearest studies we have on what cleaner classroom air does for learning. Pupils in schools with filters scored higher in maths and English. The researcher says the gains were about as large as cutting class sizes or giving pupils intensive tutoring. What happened? In October 2015, the Aliso Canyon gas storage site in Los Angeles st

Maciek Wysota · 29 October 2026 · 4 min read

What Does RESET Air Certification Actually Require?

What Does RESET Air Certification Actually Require?

Two questions come up whenever a client mentions RESET Air: What do we actually have to achieve? And what happens once we are certified? The short answer: RESET Air checks the air in your building using sensors, every month. It does not look at drawings or design plans. To get certified, the sensors must show three months in a row of good air quality. To stay certified, the air has to stay good. That is what makes RESET Air different. It is not a certificate you receive once. It is a result y

Maciek Wysota · 23 October 2026 · 4 min read

How Many IAQ Monitors Does a WELL Project Need?

How Many IAQ Monitors Does a WELL Project Need?

Two questions come up on almost every WELL project: how many indoor air quality monitors do we need, and where should they go? How many monitors does WELL require? The WELL Performance Verification Guidebook sets monitor density by occupiable area, not gross floor area: Occupiable spaceMonitor densityMinimumUnder 3,250 m²1 per 325 m²23,250 to 25,000 m²1 per 500 m²10Over 25,000 m²1 per 1,000 m²50 Round up, and apply the density across the whole project, not floor by floor. Example: a thr

Maciek Wysota · 14 October 2026 · 2 min read

From reading to seeing

Your building's air has a story. Watch it live.

Twenty minutes, your spaces, real data from a real device.